Product parameters
●Valve core: stainless steel 06Cr19Ni10 (two-way), HPb59-1 (three-way)
●Valve stem seal: four-layer V-type and O-type combined nitrile rubber seal, polytetrafluoroethylene sealing sleeve
●Valve stem: stainless steel 06Cr19Ni10
●Valve body, valve cover material: HT250
●Nominal pressure (PN): 1.6MPa
●Working medium: water, fluid temperature 5~95℃
●Valve leakage: ≤0.03%KV
●Flange standard: GB/T 17241.6 PN16

| Order code | Product Model | Valve type | DN | Connection | Bolt size | Kv value | Stroke | Dimensions | Maximum closing pressure difference [kPa] |
||||||
| L | d | D | H | H1 | |||||||||||
| 12451 | DDF-S-X-232 | 2 WAY | 32 | Flange | 4×M16 | 21 | 20 | 180 | ∅100 | ∅135 | 138 | 108 | 600 | ------ | ------ |
| 12452 | DDF-S-X-240 | 2 WAY | 40 | Flange | 4×M16 | 28 | 20 | 200 | ∅110 | ∅145 | 139 | 119 | 500 | ------ | ------ |
| 12453 | DDF-S-X-250 | 2 WAY | 50 | Flange | 4×M16 | 34 | 20 | 230 | ∅125 | ∅165 | 142 | 135 | 350 | ------ | ------ |
| 12454 | DDF-S-X-265 | 2 WAY | 65 | Flange | 4×M16 | 54 | 20 | 290 | ∅145 | ∅185 | 154 | 165 | 250 | ------ | ------ |
| 12455 | DDF-S-X-280 | 2 WAY | 80 | Flange | 8×M16 | 67 | 20 | 310 | ∅160 | ∅200 | 158 | 180 | 200 | ------ | ------ |
| 12456 | DDF-S-X-2100 | 2 WAY | 100 | Flange | 8×M16 | 120 | 40 | 350 | ∅180 | ∅220 | 200 | 200 | ------ | 300 | 500 |
| 12457 | DDF-S-X-2125 | 2 WAY | 125 | Flange | 8×M16 | 180 | 40 | 400 | ∅210 | ∅250 | 213 | 230 | ------ | 200 | 350 |
| 12458 | DDF-S-X-2150 | 2 WAY | 150 | Flange | 8×M20 | 256 | 40 | 480 | ∅240 | ∅285 | 229 | 270 | ------ | 150 | 200 |
| 12459 | DDF-S-X-2200 | 2 WAY | 200 | Flange | 12×M20 | 330 | 40 | 600 | ∅295 | ∅340 | 259 | 329 | ------ | ------ | 150 |
| 12672 | DDF-S-X-332 | 3 WAY | 32 | Flange | 4×M16 | 21 | 20 | 180 | ∅100 | ∅135 | 138 | 90 | 600 | ------ | ------ |
| 12673 | DDF-S-X-340 | 3 WAY | 40 | Flange | 4×M16 | 28 | 20 | 200 | ∅110 | ∅145 | 139 | 100 | 500 | ------ | ------ |
| 12460 | DDF-S-X-350 | 3 WAY | 50 | Flange | 4×M16 | 34 | 20 | 230 | ∅125 | ∅165 | 142 | 115 | 250 | ------ | ------ |
| 12461 | DDF-S-X-365 | 3 WAY | 65 | Flange | 4×M16 | 54 | 20 | 290 | ∅145 | ∅185 | 154 | 145 | 200 | ------ | ------ |
| 12462 | DDF-S-X-380 | 3 WAY | 80 | Flange | 8×M16 | 67 | 20 | 310 | ∅160 | ∅200 | 158 | 155 | 150 | ------ | ----- |
| 12463 | DDF-S-X-3100 | 3 WAY | 100 | Flange | 8×M16 | 120 | 40 | 350 | ∅180 | ∅220 | 200 | 175 | ------ | 250 | 350 |
| 12464 | DDF-S-X-3125 | 3 WAY | 125 | Flange | 8×M16 | 180 | 40 | 400 | ∅210 | ∅250 | 213 | 200 | ------ | 200 | 250 |
| 12465 | DDF-S-X-3150 | 3 WAY | 150 | Flange | 8×M20 | 256 | 40 | 480 | ∅240 | ∅285 | 229 | 240 | ------ | ------ | 200 |
| 12466 | DDF-S-X-3200 | 3 WAY | 200 | Flange | 12×M20 | 330 | 40 | 600 | ∅295 | ∅340 | 259 | 300 | ------ | ------ | 150 |
Installation Instructions
This series of valves is compatible with Siemens actuators.
The valve stem moves downwards in the direction of valve opening.
Before installing the valve, the pipeline should be clean and free of scale, metal flakes and other debris left during welding.
The pipeline must be concentric and free of vibration when connected to the valve body, and the water flow direction should be consistent with that marked on the valve body.
When the actuator is installed vertically on the valve body, avoid installing the actuator under the valve, and leave enough space for daily maintenance (such as disassembling the actuator).
When maintaining the valve, the power supply must be cut off or isolated, and the water system should not be under pressure.
FAQ
1.What is a 1 1 2 globe valve and what is its role in HVAC systems?
A stop valve is a valve used to control fluids. Its main function is to open or close a fluid channel and regulate flow. In HVAC systems, it is used to regulate or cut off the flow of fluids such as water, coolant, steam, etc. to ensure that the system operates as required.
2.What are the advantages of using a stop valve in HVAC systems?
The design of the stop valve gives it excellent sealing performance, which can effectively prevent fluid leakage. At the same time, its intuitive operation allows precise control of flow and is suitable for environments with various temperatures and pressures.
3.What is the difference between a Y-type stop valve and an ordinary stop valve?
The Y-type stop valve has an inclined valve body in structure, which has less resistance when the fluid passes through, so it can significantly reduce the pressure drop. In contrast, the fluid path of an ordinary stop valve is more straight or right-angled, which may result in a higher pressure drop.
4.In what cases should a 1 1 2 globe valve be selected?
The Y-type stop valve is suitable for systems that need to frequently adjust the flow and want to reduce energy consumption or pressure drop. For example, in HVAC systems with long pipes or high flow rates, the low pressure drop characteristics of the Y-type stop valve help improve efficiency.
5.Are there any requirements for the installation direction of the stop valve?
The stop valve should generally be installed in the direction of the medium flow. Most valves have an arrow on the valve body indicating the flow direction to ensure correct installation and avoid pressure differential problems in the system.
Hot Tags: 1 1 2 globe valve, China 1 1 2 globe valve manufacturers, suppliers, factory, Motorized 3 Way Valve, Motorised Ball Valve, 7 8 Refrigeration Ball Valve, 24v Digital Room Thermostat, Central Heating Room Thermostat, 410a Charging Hose